Central unit

AIO

AIO
Supply 230 V AC / 50 Hz / 127 VA
Stand-by power 12 VA
Output 24 V DC / 2.3 A
Ripple

0.4 V at 2 A load

Mode of operation monitoring Continuous duty
Mode of operation alarm Short-time duty 30 % duty cycle
Type of protection IP 30
Temperature range -5 °C … +40 °C
Housing Plastic
Colour Grey (~ RAL 7035)
Show more information
Request & 
Compare

Add to comparison list / Remove from comparison list
Request

  • Central unit for smoke exhaust and ventilation in the lift shaft

  • Integrated emergency battery power supply (required for on-site NSHEVs and thermo flaps as well as louvre windows)

  • Smoke detector remote reset, cable monitoring for short circuit and recess

  • Integrated earth fault monitoring and LED test

  • Integrated temperature sensor

  • Connection option for acoustic alarm devices

  • Connection option for temperature regulator and air quality sensor

  • Isolated signalling contact for alarm and fault messages to the lift controller

  • 2 smoke detection lines (shaft and machine room)

  • 2 drive groups for connection of spring return motors or 24 V DC SHEV drives

  • Radio reception unit for communication with the lift status reporting units

  • 2 inputs for connection of the contacts provided by the lift controller for lift tension and maintenance mode

  • Connections of all components via RJ45 connectors

  • Fault and alarm indicator (LED) individually for each cable connection

Details of approval on request.

Instructions
2.52 MB